Your Equation

Library / Control engineering / CTL-06

Control engineering

Damping ratio from measured overshoot

Inverse of the overshoot formula: the damping ratio that gives a measured percentage overshoot in a standard second-order step response.

Ref
CTL-06
Rev
v1
Field
Control engineering
Result
ζ

This is the overshoot formula Mp = e−πζ/√(1−ζ²) solved for ζ. Enter the overshoot as a percentage of the final value, read from a step response. The result is the damping ratio of the second-order model that would overshoot by that much.

Inverse of the overshoot formula: the damping ratio that gives a measured percentage overshoot in a standard second-order step response.

Calculator

Solve for
%
160
  • Natural logarithm of the overshoot fraction, ln(Mp/100)−1.814
  • Pole angle from the negative real axis, cos⁻¹ ζ60 °
  • Rule-of-thumb phase margin, 100ζ (reasonable below about ζ = 0.6)50 °

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Damping ratio () current value 0.5
MpPercentage overshootKey driver
0.160.826
  • An overshoot of 16.3 % corresponds to ζ ≈ 0.5. Overshoots of 5 % and 25 % correspond to ζ ≈ 0.69 and 0.404.
  • Halving the overshoot to 8.15 % raises the required damping from 0.5 to 0.624. The overshoot is very sensitive to damping, so a small change in ζ makes a large visible difference.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing ()Local stepChange in result
Mp Percentage overshoot1 to 60 %0.16050.82610.6656+10%−4.02 %

Sweep of Percentage overshoot

Percentage overshoot (%)Damping ratio
10.8261
8.3750.6196
15.750.5071
23.130.4225
30.50.3536
37.880.2953
45.250.2447
52.630.2002
600.1605

Sweep one variable

Damping ratio ()Hover, touch, or use the arrow keys on the chart
0.20.40.60.8 102030405060 Percentage overshoot (%) now 0.5

Variables and how each one contributes

ζ

Damping ratio

Result ·

What the equation gives you. Everything else feeds it.

Mp

Percentage overshoot

% · typical 1 to 60

The percentage overshoot: (peak − final value) / final value × 100. More overshoot means less damping, but ζ changes more slowly with overshoot at the high end. Raising it by 10 % (to 17.93) moves the result by −4.02 %, from 0.5 to 0.4799.

Worked example with the values above

  1. Logarithm of the fraction: ln(0.163) = −1.814.
  2. Denominator: √(π² + ln²) = √(9.87 + 3.291) = 3.628.
  3. ζ = −(−1.814) / 3.628 = 0.5.

Assumptions and limits

  • The system behaves like a standard second-order system with no zeros, so that overshoot depends on ζ only.
  • A step from rest, measured from a record with the final value reached.

Common mistakes

  • Entering the overshoot as a fraction (0.163) when the input is a percentage (16.3).
  • Applying it to a loop with a zero or a slow extra pole, where the overshoot says little about the true damping.

Statistics and uncertainty

A step response with noise gives an overshoot that is biased high, so it should be measured on a smoothed record and ideally averaged over several steps. Because ζ comes from a logarithm of the overshoot, an error in a small overshoot (a few per cent) matters much more than the same absolute error in a large one.

Where it is used

  • Identifying the damping of a servo, vehicle or actuator from a recorded step.
  • Converting an overshoot specification into a damping ratio for design.

Maths you need

  • Natural logarithm: the inverse of the exponential
  • Step response of a second-order system: peak overshoot Mp

Related formulas

Practise this formula