Convective heat transfer

Heat flow between a surface and a moving fluid.

Ref
MEC-08
Rev
v1
Field
Mechanical
Result
Q̇ [W]

Q̇ in watts, h film coefficient in W/(m²·K), A surface area, Ts surface temperature and T_∞ the bulk fluid temperature.

A surface loses heat to the air or water flowing past it in proportion to its area, the temperature difference, and a film coefficient that describes how effectively the flow carries heat away.

Calculator

Solve for
W
W/(m²·K)
51,000
m²
0.0150
°C
30120
°C
−1030
  • Heat flux1,000 W/m²
  • Thermal resistance 1/(hA)0.02 K/W

What drives the result

Each variable is moved across its typical range while the others stay at the values above. The longest bar is the key driver.

Heat flow (W) current value 2,000 W
hFilm coefficientKey driver
40080,000
ASurface area
1050,000
TsSurface temperature
5005,000
T∞Fluid temperature
1,5003,500
  • The film coefficient is the hard part. It depends on the flow speed, fluid and geometry, and can only be estimated from correlations or tests.
  • Doubling the air speed does not double h; for turbulent flow it rises roughly as speed to the 0.8 power.
  • Surface and air temperature difference sets the rate; a hot component in cool moving air loses heat quickly.
Chart data as tables

Ranked variables

VariableTypical rangeLowest resultHighest resultSwing (W)Local stepChange in result
h Film coefficient5 to 1,000 W/(m²·K)40080,00079,600+10%+10 %
A Surface area0.01 to 50 m²1050,00049,990+10%+10 %
Ts Surface temperature30 to 120 °C5005,0004,500+10%+15 %
T∞ Fluid temperature−10 to 30 °C1,5003,5002,000+10%−5 %

Sweep of Film coefficient

Film coefficient (W/(m²·K))Heat flow (W)
5400
9.696775.7
18.81,504
36.462,917
70.715,657
137.110,970
265.921,270
515.741,250
1,00080,000

Sweep one variable

Heat flow (W)Hover, touch, or use the arrow keys on the chart
020k40k60k80k 520100500 Film coefficient (W/(m²·K)), log scale now 2,000

Variables and how each one contributes

Q̇

Heat flow

Result · W

What the equation gives you. Everything else feeds it.

h

Film coefficient

W/(m²·K) · typical 5 to 1,000

Still air about 5–10, forced air 25–250, water 500–10 000. Directly proportional; the most uncertain input.

A

Surface area

m² · typical 0.01 to 50

Area in contact with the fluid. Directly proportional; fins increase it.

Ts

Surface temperature

°C · typical 30 to 120

Temperature of the solid surface. Linear through ΔT.

T∞

Fluid temperature

°C · typical −10 to 30

Bulk temperature of the passing fluid. Linear, opposing Ts.

Worked example with the values above

  1. Temperature difference: 60 − 20 = 40 K.
  2. Q = hAΔT = 25 × 2 × 40.
  3. Q = 2,000 W.

Assumptions and limits

  • Steady state.
  • Uniform surface temperature and a constant h.
  • Radiation is neglected.

Common mistakes

  • Using the wrong h for the flow regime.
  • Forgetting that radiation can add 20–50% at high surface temperatures.
  • Using the fluid’s temperature near the wall rather than the bulk.

Statistics and uncertainty

The film coefficient from correlations is typically uncertain by ±20–25%, which dominates any measurement error in the temperatures. Treat the result as an estimate, and add margin in cooling designs.

Where it is used

  • Cooling of electronics and engines.
  • Heat loss from pipes and hulls.
  • Heat soak in sensor housings.